mains-mains - ATS107DMS
ATS modules
ATS107DMS Description
The configurable ATS controller model ATS107DMS allows for many of the demanding applications in the modern power supply network to be achieved.The ATS107DMS is designed as an end of line transfer controller between two power supplies of typically similar security and availability.It includes single phase sensing and timing functions to take account of PREFERRED SUPPLY FAILED delay and RETURN TO PREFERRED SUPPLY delay as well as the delay between control outputs to take consideration of contactor operating times. Inputs are provided for the remote selection of the PREFERRED SUPPLY and RETURN INHIBIT.
How it works
Under normal conditions with the default preferred supply as SUPPLY 1 and that supply is being available, the SUPPLY 1 output relay would be energized closing the SUPPLY 1 contactor 1 and connecting SUPPLY 1 to the load. When SUPPLY 1 becomes unavailable, the preferred supply failed delay timer is initiated and should it time out, the SUPPLY 1 output relay would be de-energized opening the SUPPLY 1 contactor 1 and disconnecting SUPPLY 1 from the load. After the internal switching delay and considering SUPPLY 2 is available, the SUPPLY 2 output relay would be energized closing the SUPPLY 2 contactor 2 and connecting SUPPLY 2 to the load. On return of SUPPLY 1 to a healthy state the return to preferred supply delay timer is initiated and should it time out successfully without disturbance, the SUPPLY 2 output relay would be de-energized opening the SUPPLY 2 contactor 2 and disconnecting SUPPLY 2 from the load. After the internal switching delay and considering SUPPLY 1 is within range, the SUPPLY 1 output relay would be energized closing the SUPPLY 1 contactor 1 and re-connecting SUPPLY 1 to the load. If the return inhibit was applied whilst ALTERNATIVE SUPPLY is on load, on return of PREFERRED SUPPLY to a healthy state the controller would however remain on ALTERNATIVE SUPPLY until RI push button is pressed again making return inhibit function inactive.Time delays are set via 5 pole DIP switch fitted on the right top corner of the controller and selection possible as per TABLE “A” and “B”, typically the return to preferred supply delay is TWICE the preferred supply failed delay.
Specifications
DC Supply: 12Vdc or 24Vdc (8...40Vdc)
Min. standby current: 0.07mA @12Vdc (0.05mA @24Vdc)
AC voltage input (SUPPLY 1): 100...300Vac
AC voltage input (SUPPLY 2): 100...300Vac
Frequencies supported: 50Hz / 60Hz
Dimensions: 95x90x40mm
Operating temperature range: -30 to +70°C
Humidity Range Operating: 20-80%